This paper mainly describes the typical design scheme of Ankerui fire emergency lighting and evacuation indication system. 1. Design of luminaire layer a. Select the main evacuation port and evacuation channel according to the plan plan. Design the emergency sign according to the fire evacuation instruction system design specification and local design standards. Lamp Steel Drill Bits,3 Blades Pdc Drill Bits,Forging Casting Drill Bits,3 Blades Drill Bits J.B Machinery (Ningbo) Co., Ltd. , https://www.jbdrill.com
b. Design the density and position distribution of emergency lighting fixtures according to the project emergency lighting illumination requirements;
c. According to the plane fire zone, the circuit is divided. It is not allowed to share one circuit with multiple fire zones. Each vertical evacuation channel and its extension zone may be considered as a separate fire zone and shall be vertically lit;
d. Single-circuit emergency luminaries should not be larger than 32.
2. System topology diagram A100 fire emergency lighting and evacuation indication system topology diagram is used to reflect the system structure of the whole project, from which the connection relationship between all layers of the A100 system in the system and the emergency lighting controller to the fire emergency lighting can be read. The emergency power supply wiring can clearly indicate the distribution position of the emergency lighting distribution electric device and the number of various emergency lighting fixtures.